GLEDHILL REPAIRS

 gledhill pulsacoil 2000 repairs  , no inhibitor introduced, limescale attacked immersion heater, lower immersion  unit  fell to bits flooding the kitchen below !! i always advise that fernox f1 is introduced into the store to stop this occuring again. RAYLIEGH,ESSEX

gledhill boilermate 2000 repairs , main feed and expansion tank supply had been isolated and store had run low giving spasmodic hot water, refilled store and added fernox f1 , tested, left in working order.HAMPTON VALE ESTATE PETERBOROUGH

gledhill boilermate 2000 repairs, with "switch" facillity, this enables the store to change to electic only, if your gas or oil boiler fails, and will still give heating /hotwater. the heater bottle carries 2x 4.5 kw heater coils, one of which had blown,causing damage to the main pcb and fuse carrier. replaced heater bottle, main pcb, and fuse carrier. left in working order. HARROW.

gledhill pulsacoil 2000 repairs, 3kw immersion heater removed. it has been attacked by limescale , i cant undrstand why installers never introduce any inhibitor in the first place, cost probably, but not cost effective for the owner.i always advise fernox f1. replaced , added fernox, refilled store and tested.DOWNHAM MARKET, NORFOLK.

gledhill electramate repairs main pcb, looks visually fine from the front.

the rear shows a different story. power spikes during the night on economy 7 tariff causing main relay failure, making relays stick on .  THETFORD ,SUFFOLK.

continually sending 240 v to main pcb.This became a problem for the whole housing estate around 50 flats have suffered with this problem, luckily it has been rectified by the electrical  supplier.

LEAKING IMMERSION HEATER FROM A ELSON CORAL E

YOU CAN SEE IT DRIPPING AT THE BOTTOM OF THE HEATER

AGAIN LIMESCALE HAS ATTACKED THE HEATER INTERNALLY,

DUE TO NO INHIBITOR INTRODUCED FROM INSTALLATION.

AGAIN THIS IS THE BOTTOM IMMERSION HEATER FROM THE SAME ELSON UNIT, WHITE/GREEN BUILDUP IS LIMESCALE AND AGAIN LEAKING AT THE BOTTOM OF HEATER.BOTH IMMERSIONS HAD TO BE REPLACED AND FERNOX  F1 INHIBITOR WAS INTRODUCED. CHESTERTON, CAMBRIDGE.

GLEDHILL BOILERMATE REPAIRS  "SWITCH" HEATING ELEMENT  9KW READY FOR INSTALLATION. FERNDALE ESTATE, YAXLEY, PETERBOROUGH.

GLEDHILL BOILERMATE / PULSACOIL  REPAIRS ELECTRAMATE  AND PULSACOIL PLATE HEAT EXCHANGER, USUAL FAILURE IS DUE TO LIMESCALE BUILDING UP INTERNALLY, USUAL SYMPTOMS ARE REDUCED HOT WATER PRESSURE AT THE TAP AND INTERMITTENT HOT WATER, CAN BE DESCALED OR REPLACED FAIRLY EASY.ferndale estate ,yaxley, peterborough.

IMMERSION HEATER REMOVED FROM A GLEDHILL PULSACOIL, THE MAIN ELEMENT HAS FAILED AND HAS LEAKED STORE WATER ONTO THE ELECTRICS[ WHITE/GREEN BUILDUP IS LIMESCALE. REPLACED AND REFILLED WITH FERNOX F1, LEFT IN WORKING ORDER. ST NEOTS CAMBRIDGESHIRE.

 gledhill pulsacoil 111 repairs, 240 volts to thermal store wiring but led on  pump speed control board  emitting a permanent red led, microprocesser crashed. replaced and left working.SANDY, BEDFORDSHIRE.

gledhill boilermate 11 ,customer complained of a burning smell when the unit was switched on as their gas boiler was giving problems, and had switched on the immersion for hot water and heating. drained down and added fernox f1 and fitted new immersion, refilled and tested, left in working order. BOSTON,LINCOLNSHIRE.

 pulsacoil 111. leaking immersion heater, drained down and removed defective immersion heater, removed sludge buildup, introduced fernox f1 inhibitor , refilled and tested, left in working order. CAMBOURNE, CAMBRIDGESHIRE.

ECONOMY 7 POWER SPIKES AGAIN, THIS TIME IN ST MARYS ISLAND, CHATHAM,KENT.

replaced both relays, relay boards and rewired, tested, left in working order.

IMMERSION HEATER REMOVED FROM A PULSACOIL 3 AS USUAL NO INHIBITOR WAS INTRODUCED INTO THE STORE FROM BEING INSTALLED AND OVER TIME THE LIMESCALE PRESENT IN THE STORED WATER HAS ATTACKED THE REAR OF THE IMMERSION BASE CAUSING IT TO LEAK ONTO THE 240 VOLT ELECTRIC SUPPLY, TRIPPING THE FUSE. THIS IS A VERY COMMON PROBLEM , BUT EVERYBODY SEEMS TO BLAME IT ON  THE GLEDHILL UNIT, WHEN IN FACT ITS  DOWN TO THE LOCAL PLUMBERS WHO HAD INSTALLED THEM NOT ADDING ANY PROTECTION TO THE STORE.  NEPTUNE CLOSE, IPSWICH.

 ELECTRAMATE 2000 PUMP JAMMED AND BURNT OUT. REPLACED PUMP AND TESTED SYSTEM. ANOTHER HAPPY CUSTOMER . KINGSWAY, FINCHLEY, NORTH LONDON.

 PULSACOIL 3 LOWER IMMERSION TRIPPING FUSES. THIS IS THE USUAL SLUDGE BUILD UP FROM AN IMMERSION WHICH HAS FAILED INTERNALLY.I HAD TO REMOVE THE DRAIN POINT  AS THE WASHER WAS SEIZED INSIDE AND THE STORE WOULD NOT DRAIN. CAMBOURNE , CAMBRIDGESHIRE.

ELECTRAMATE 2000 SHOWING ZERO PRESSURE IN STORE. AFTER INITAL CHECKS FOUND THAT THE BACKFLOW PREVENTION VALVE HAD BEEN SWITCHED OFF, REFILLED SYSTEM TO 1 BAR [COLD] AND LET THE STORE SETTLE FOR 20 MINS. FOUND 5 LEAKING PUMP VALVES, THAT HAD STEADILY DROPPED THE STORE PRESSURE.DRAINED AND REPLACED ALL PUMP VALVES . REFILLED STORE AND TESTED,LEFT IN GOOD, CLEAN , WORKING ORDER. RAVENSWOOD ESTATE, IPSWICH, SUFFOLK.

 ELSON CORAL E LEAKING FROM LOWER IMMERSION HEATER.

REPLACED AND TESTED. LONDON NW3.

 gledhill repairs in north london, commisioning new acb on boilermate 2000. willsden.

boilermate/ pulsacoil, repairs, north london.










this pulsacoil 2000 was in a rented flat in wilkinson drop, hadliegh, essex. the tenant did not know that the feed tank needed checking and due to the lower immersion leaking badly, the store emptied itself and dry fired the upper immersion which was also leaking and sending 240 volts continually to the heater, this then overheated and caught light to a towel placed on top of the unit, and the fire brigade were called and had to smash down the front door to get in !! somebody called h--e serve had been to this appliance and left the feed tank empty and still leaking, and told my client it was ok to use !!!!!  very dangerous. all now up and running !

 

boilermate 2 leaking immersion has lead to total rusting of the outer casing.

my customer was advised that the unit needed replacing at a cost of £3,000 by a local heating and plumbing company.after intial checks found to be the element leaking, drained down store and replaced element. a very happy customer , GREAT WOODCOTE PARK, LOUGHTON, ESSEX.

 

if you would like me to carry out repairs to your gledhill  thermal store or elson thermal store then please call


MOBILE - 07757076530
MOBILE - 07967424232
MARK.

 and ask for GLEDHILL service engineer.

 

fernox  thermal store protection stops limescale build up.

sentinel thermal store protection stops limescale build up.